I/O-Modules
Fieldbus Terminals
Relay Output Terminal 230 V AC, 2 A

Product Description

The KL2602 output terminal switches two relays with one single contact each, controlled by
the control system. The relay contact is connected to the power contact, which can be used
up to 230 V AC, and can be used universally to switch mains voltage loads. The KL2612 and
KL2622 bus terminals feature potential-free contacts. The power contact is not looped
through. The bus terminals indicate their signal states with LEDs.

Technical data

KL2602 KL2612 KL2622

Number of outputs

2 x normally-open to power contact 2 x change over 2 x normally open

Rated load voltage

230 V AC / 30 V DC 125 V AC / 30 V DC 230 V AC / 30 V DC

Switching current resistive

5 A AC / DC 0.5 A AC / 1 A DC 5 A AC / DC

Switching current inductive

2 A AC / DC not applicable 2 A AC / DC

Switching voltage minimum

10 mA at 5 V DC 10 m A at 10 mV 10 mA at 5 V DC

Electrical isolation

500 Vrms (K-Bus / field voltage)
Current consumption from K-Bus 80 mA 60 mA 85 mA
Operating cycles mech. (min.) 2 x 107 1 x 108 2 x 107
Operating cycles electr. (min.) 1 x 105 (5 A / 30 V DC) 2 x 105 (1 A / 30 V DC) 1 x 105 (5 A / 30 V DC)
Bit width in the process image 2 O
Configuration no address or configuration setting

Weight approx.

85 g 80 g 80 g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95%, no condensation

Vibrations/Shock resistance

conforms to IEC 68-2-6 / IEC 68-2-27

EMC resistance burst / ESD

conforms to EN 50082 (ESD, Burst) / EN 50081

Installation position

any

Type of protection

IP20

 

back | Fieldbus Terminals | Download | Home

Copyright © 2000 TRS Fieldbus Systems, Inc. All rights reserved.