Relay Output Terminal 400 V AC, 3 A

Product Description

The KL2631 output terminal switches a relay with one single contact, controlled by the
control system. The relay contact is connected to the power contacts, which can be used up
to 400 V AC, and can be used universally to switch mains voltage loads. The bus terminal
indicates its signal status by a LED. The KL2631 bus terminal must be supplied via the
feed-in terminal KL9190 for use of high voltage up to 400 V AC.

Technical data

KL2631

Number of outputs

1 x normally-open to power contact

Rated load voltage

400 V AC / 300 V DC

Switching capacity DC

300 V = 0.15 A; 24 V = 5 A; non lineaer

Switching capacity AC

power contact

Switching voltage minimum

(short-circuit-protected)

Electrical isolation

500 Vrms (K-Bus / field voltage)

Current consumption from K-Bus

80 mA
Operating cycles mech. (min.) 107
Operating cycles electr. (min.) 1,3 x 105 (2 A / 250 V AC)
Bit width in the process image 2 O
Configuration no address settings, configurations via bus coupler or control system

Weight approx.

85 g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95%, no condensation

Vibrations/Shock resistance

conforms to IEC 68-2-6 / IEC 68-2-27

EMC resistance burst / ESD

conforms to EN 50082 (ESD, Burst) / EN 50081

Installation position

any

Type of protection

IP20

 

back | Fieldbus Terminals | Download | Home